Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0324-00513
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2024 | Commercial Building | APPROVED | |||
| 04/09/2024 | Commercial Electrical | APPROVED | |||
| 04/10/2024 | Commercial Mechanical | APPROVED | |||
| 04/08/2024 | Site Zoning | APPROVED | |||
| 04/10/2024 | Water - PDSD | APPROVED | |||
| 04/05/2024 | Site Engineering | NOT REQUIRED | |||
| 04/10/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/10/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Revise the location of the sediment trap to be downstream of the appliance shut off valve, as close to the equipment as possible. Reference: Section 408.4, IFGC 2018. 2. Verify that the distance from the hot water source to the hot water termination for the relocated lavatory complies with the requirements of Section C404.5, IECC 2018. |
||
| 03/25/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 03/25/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |