Permit Number: TC-COM-0324-00513
Parcel: 11615077K

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0324-00513
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2024 Commercial Building APPROVED
04/09/2024 Commercial Electrical APPROVED
04/10/2024 Commercial Mechanical APPROVED
04/08/2024 Site Zoning APPROVED
04/10/2024 Water - PDSD APPROVED
04/05/2024 Site Engineering NOT REQUIRED
04/10/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/10/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Revise the location of the sediment trap to be downstream of the appliance shut off valve, as close to the equipment as possible. Reference: Section 408.4, IFGC 2018.
2. Verify that the distance from the hot water source to the hot water termination for the relocated lavatory complies with the requirements of Section C404.5, IECC 2018.
03/25/2024 Fire New Construction REVIEW COMPLETED
03/25/2024 PDSD Application Completeness Express REVIEW COMPLETED