Permit Number: TC-COM-0324-00505
Parcel: 112063360

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0324-00505
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2024 Commercial Electrical APPROVED
04/10/2024 Commercial Plumbing APPROVED
04/09/2024 Water - PDSD APPROVED
04/05/2024 Site Engineering NOT REQUIRED
04/10/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/08/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
Sheet A1.0: Please amend plan to provide a drawing detail for the new wall assembly “C” to include attachment at the top and bottom of the wall to existing structure . Additionally, please provide the ESR report or a stud height chart for the metal wall studs indicating the allowable height for the specified studs IBC 1605.15
Sheet A5.2: Please amend plan to clarify the finishes for the bathroom walls as Sheet A1.0 Demolition Scope note #7 indicates the wall finishes to be removed and a note on sheet A5.2 states Existing wall finishes to remain. IBC 107.2.1
1. IEBC 305.7 requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, and signs. If these items are in full compliance with the current code, provide a statement indicating which of these items are in compliance on the cover sheet of the drawings. Otherwise, accessibility upgrades shall be required in accordance with for the balance of the items not in compliance. IEBC.305.7. For example, the restroom facilities do not appear to be accessible.

A. If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs. If this exemption is taken, accessibility upgrades equaling 20% of the cost of the project shall be made.
Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
04/10/2024 Commercial Mechanical REQUIRES RESUBMIT Provide heating and cooling load calculations to justify the addition of the split-system heat pump to the existing HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
04/08/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0324-00505
2470 N CAMPBELL AV – C-1
Food Service (1st Review)

TRANSMITTAL: April 8, 2024

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). Food service is a allowed use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5 and 4.9.13.O.

1. Zoning was not able to find approved plans showing the 600 SF patio. Either provide an approved site plan showing the patio or a development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

2. Provide a wheel stop location dimension for the new wheel stop called out under Keynote 20.

3. Provide a detail for the proposed accessible sign called out under Keynote 19.

4. The proposed accessible sign called out under Keynote 19 appears to encroach into the 2’-6” vehicle overhang. Clearly demonstrate that the sign does not encroach into the 2’-6” overhang area.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/26/2024 Fire New Construction REVIEW COMPLETED
03/22/2024 PDSD Application Completeness REVIEW COMPLETED