Permit Number: TC-COM-0324-00499
Parcel: 133050960

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0324-00499
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2024 Commercial Electrical APPROVED
04/23/2024 Commercial Structural APPROVED
04/22/2024 Site Engineering NOT REQUIRED
04/23/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/23/2024 Commercial Mechanical REQUIRES RESUBMIT Verify that the bathrooms have exhaust fans for ventilation per Table 403.3.1.1, IMC 2018.
04/23/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Reference: Section 419.6, IPC 2018 as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide shower valves that comply with the requirements of Section 412.3, IPC 2018.
3. If the new showers do not have prefabricated receptors, provide details to show that the construction of the receptors complies with the requirements of Section 421.5, IPC 2018.
4. Clarify the revisions to the waste and vent piping in the bathrooms. Show that each trap and trapped fixture has been vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2018.
04/02/2024 Fire New Construction REQUIRES RESUBMIT Please provide condition for occupancy classification. Provide permit number for existing fire sprinkler system and fire alarm system.
Questions: patricia.shelton@tucsonaz.gov
04/18/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Lead Planner

PROJECT: TC-COM-0324-00499
8855 East Calle Bogota – R-1
Residential Care Services (1st Review)

TRANSMITTAL DATE: April 18, 2024

Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

1. State the applicable Residential Care Services land use type on the site plan. Both Adult Care Service and Physical and Behavioral Health Service uses are permitted in the R-1 zone, subject to use-specific standards 4.9.7.J.2.a, .3.a, and .4.

2. Per Tucson Unified Development Code (UDC) Table 7.4.4-1, four motor vehicle parking spaces are required for Residential Care Services uses with six to ten residents. Show the four required motor vehicle parking spaces on the site plan. Up to 50% of the parking required may be on-street parking if located on the same side of the street as the use and does not extend beyond the street frontage of the subject property (UDC 7.4.5.C).

If you have any questions about this transmittal, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.
04/23/2024 Water - PDSD REQUIRES RESUBMIT Revise the plot plan to show the location of the reduced pressure backflow prevention assembly. Reduced pressure backflow prevention assemblies are required at the water meter for licensed, personal care facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf.
03/22/2024 PDSD Application Completeness Express REVIEW COMPLETED