Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0324-00499
Parcel: 133050960

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0324-00499
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2024 Commercial Building APPROVED
08/07/2024 Commercial Electrical APPROVED
08/07/2024 Commercial Mechanical APPROVED
08/07/2024 Commercial Plumbing APPROVED
08/07/2024 Site Zoning APPROVED
08/07/2024 Water - PDSD APPROVED
08/08/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/08/2024 Fire New Construction REQUIRES RESUBMIT The existing fire sprinkler system will need to be upgraded to an NFPA 13R to accommodate an R-4 Condition 2 Occupancy (IFC, 903.3.1.2). Please note this requirement on plans.
Questions: patricia.shelton@tucsonaz.gov
07/23/2024 PDSD Application Completeness Express REVIEW COMPLETED