Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0324-00495
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/04/2024 | Commercial Electrical | APPROVED | |||
04/09/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
04/09/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Show how a future tenant will be able to justify 9-tons of cooling for a 1443 square foot suite. Reference: Section C403.1.1 and C502.2.3, IECC 2018. | ||
03/21/2024 | PDSD Application Completeness | REVIEW COMPLETED | Addressing issue concerning the unit/suite listed on the plan set. Plans list Suite/Unit E100 and the suite/unit specified is not attached to the address. A pre issuance addressing condition has been placed on permit. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and or add the suite/unit. |