Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0324-00495
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/24/2024 Commercial Mechanical REQUIRES RESUBMIT Even assuming that the “150 ton/square foot” tenant requirement is a typographical error, the comment is not resolved. Provide heating and cooling load calculations in accordance with ANSI/ASHRAE/ACCA Standard 183 or other approved calculation procedure to justify the output capacity of the existing and proposed HVAC equipment. Reference: C4031.1, C403.3.1, and C502.2.3, IECC 2018. [Initial comment: Show how a future tenant will be able to justify 9-tons of cooling for a 1443 square foot suite. Reference: Section C403.1.1 and C502.2.3, IECC 2018.]
04/10/2024 PDSD Application Completeness Express REVIEW COMPLETED Addressing issue concerning the unit/suite listed on the plan set. Plans list Suite/Unit E100 and the suite/unit specified is not attached to the address. A pre issuance addressing condition has been placed on permit. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and or add the suite/unit.