Permit Number: TC-COM-0324-00489
Parcel: 13316049B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0324-00489
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2024 Site Zoning APPROVED
04/22/2024 Site Engineering NOT REQUIRED
04/24/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/24/2024 External Reviewers - Stantec REQUIRES RESUBMIT April 10, 2024
1st Review

Pate Contractors, LLC
Attn: John Eden
1129 N. Winstel Blvd.
Tucson, Arizona 85716

Re: FIRST AMERICAN TITLE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0324-00489
Stantec Project Number: 185215066
Stantec File Number: TUC-24-034

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 4,880 33 Yes No
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system is to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

Sheet A4

1. The existing bathroom prior to the demo and remodel appeared to have qualified for exception 1 of Section 1109.2 of the International Building Code, due to the remodel this restroom is no longer accessed only through a private office. The restroom must now meet accessibility requirements of ICC A117.1-2009.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.



Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/01/2024 Fire New Construction REVIEW COMPLETED
03/21/2024 PDSD Application Completeness Express REVIEW COMPLETED