Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0324-00484
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/24/2024 | Site Zoning | APPROVED | |||
09/24/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/29/2024 | External Reviewers - Stantec | REQUIRES RESUBMIT | August 28, 2024 2nd Review Seaver Franks Architects Attn: Rick Huch/Hillary Grigel 2552 N. Alvernon Way Tucson, Arizona 85712 Re: STAR PASS NEW EGRESS PATH City of Tucson Permit Number: TC-COM-0324-00484 Stantec Project Number: 185215066 Stantec File Number: TUC-24-033 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms U V-B N/A N/A No No Separate Permits: None. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet A0.0 1. Addressed. 2. New Comment: The revised plan-set is missing Sheet A2.3. Please provide. Sheet A2.1 1. Addressed. Sheet A2.2 1. Addressed. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS Sheet E1.0 1. Addressed. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
09/24/2024 | Site Engineering | REQUIRES RESUBMIT | See Zoning comments from 4/19/24: 1. Per UDC Article 3.3.3.G.2.A: A site plan (Development Package) is required for the following types of development: c. Existing development undergoing a change of use , building or structure additions, and/or a reconfiguration of an area outside a building ; |
||
08/23/2024 | PDSD Application Completeness | REVIEW COMPLETED |