Permit Number: TC-COM-0324-00453
Parcel: 119421840

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0324-00453
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2024 Site Zoning APPROVED
04/24/2024 Site Engineering NOT REQUIRED
04/24/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/10/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 4/6/2024 12:14:11 AM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 4/2/2024 5:09:52 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 4/8/2024 7:05:28 PM
1. Plan sheet M-4.1 - Rooftop HVAC Unit Schedule states RTU #1 under MIN OA (CFM) 510 CFM. Outside Air Schedule under Required Outside Air (CFM) total OA CFM for RTU #1 equals 527 CFM. Other RTU do not match OA requirements. Confirm all OA CFM quantities for al RTU - 2015 IBC Section [A]107.2.1Information on construction documents.

2. Plan sheet M-4.1 - Rooftop HVAC Unit Schedule states RTU #2 under Air Flow (CFM) 2475 CFM. Total SAD (supply air drops) CFM quantity for RTU #2 on Plan Sheet M-2.1 equals 2295 CFM. Confirm CFM quantities for RTU #2 - 2015 IBC Section [A]107.2.1Information on construction documents.

3. Plan sheet M-4.1 - Rooftop HVAC Unit Schedule states RTU #4 under Air Flow (CFM) 2225 CFM. Total SAD (supply air drops) CFM quantity for RTU #4 on Plan Sheet M-2.1 equals 1980 CFM. Confirm CFM quantities for RTU #4 - 2015 IBC Section [A]107.2.1Information on construction documents.

4. Plan Sheet M-5.1 - Confirm the CFM on the Mechanical Compliance Certificate. Confirm the stated Constant Volume CFM for RTUs #2 and #4 - 2015 IBC Section [A]107.2.1Information on construction documents.



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 3/26/2024 6:12:14 PM




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 4/9/2024 9:20:42 PM
First Plumbing Review:
1). Sheet P-6.1:The gas code and selected needs to derive from the current adopted gas code. Add the current adopted gas code & sizing table to the gas load summary in accordance with -2018 IFGC 402.3

2). Sheet P-5.1: The detail page is missing a detail that properly depict the installation of the SEP-1 lift tank & pump connections & vent. Add a lift pump/tank detail in accordance with -IPC 712.2, 712.3.2

3). General: Provide age range of the children to to determine the fixture spacing complies with -2009 ICC A117.1
04/24/2024 Water - PDSD REQUIRES RESUBMIT Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
04/14/2024 Fire New Construction REVIEW COMPLETED
03/25/2024 PDSD Application Completeness REVIEW COMPLETED