Permit Number: TC-COM-0324-00443
Parcel: 112054130

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0324-00443
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2024 Fire New Construction NOT REQUIRED
04/04/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/04/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
Sheet SS-00: Please amend plans to update State and California Code references to the 2018 International Building Code. IBC 107.2.1
Please provide Geotechnical Report prepared by Terracon and dated 07/13/2023, with the next submittal IBC 107.2.1

Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
03/28/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. Ref; Plan sheet E-201 Single Line Diagram.

1a. Tucson Electric Power normally does not provide or install conduit and secondary service conductors for commercial 3 phase electrical services. Please indicate on the plans, conduit, conductor sizes, quantities and types for the service secondary feeders.

1b. Is ‘SB-1’ a 3 phase service? Indicate this in the equipment description note.

1c. Indicate primary and secondary feeder sizes for the transformer ‘SD-XR’ on the plans.

2. Provide evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code (OLC). See section 104 for plan submittal requirements.

3. Provide site lighting plans with the following information on the plans;

(a) Provide a complete luminaire schedule.

(b) Full compliance with sections 104.2.1(1), (2), (3).

(c) See table 401.1, Include parcel size, lighting area and option, and indicate this information in the lighting site plan.

4. 402.1 (light source color temperature requirements), shielding requirements, etc .

5. Provide calcs for total lumens allowed and total lumens proposed per acre for Full Cut Off and Unshielded per table 401.1.Must include existing to remain lighting.

6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

7. Specify any exceptions used.

8. Provide Curfew lighting controls If applicable Per section 403(OLC) and NEC 225.31, 32.

9. Provide complete compliance with the 2018 IECC for the interior and exterior lighting where applicable.

10. Do not confuse the Outdoor Lighting Code with the IECC.

11. The cover plan sheet G-001 ‘System Summary’ show 86 PV Modules and Plan sheet ‘E-101’ ‘Mounting Plane I.D.’ shows 84 PV Modules. Please clarify.

Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.
04/02/2024 Site Engineering REQUIRES RESUBMIT Tucson codes and ordinances can be found online at https://codelibrary.amlegal.com/codes/tucson/latest/overview

Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted in the TDC Online Portal.

Lianne Evans
lianne.evans@tucsonaz.gov
04/03/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-0324-00443 & TC-COM-0324-00444
2956 N CAMPBELL AV. – C-1
EV Charging Stations & Solar Canopy (3rd Review)

TRANSMITTAL DATE: April 3, 2024

Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

The site is in the C-1 zone (UDC 4.7.20).

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The Administrative Manual can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes-and-Plans/Zoning-Code#section-1.

If you have any questions about this transmittal, contact Nicholas Martell at Nicholas.Martell@tucsonaz.gov.
.
03/18/2024 PDSD Application Completeness Express REVIEW COMPLETED