Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0324-00439
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/15/2024 | Site Engineering | NOT REQUIRED | |||
04/17/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
04/02/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Nicholas Baptiste njnobaptiste@safebuilt.com Approved Reason: Date Completed : 3/27/2024 9:06:09 PM Building(B) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 3/18/2024 3:57:52 PM 1. General: Provide the lighting details showing compliance with the 2018 IECC section R404 2. Sheet G1.030: Show the full means of egress path. The plans do not include the route and location of the second means of egress. (2018 IBC sections 107, 1002.2, 1017) 3. Sheet G1.030: the General Notes reference sheet G0.003 but this sheet was not included in the set. (2018 IBC section 107) 4. Sheets G1.030, A1.030: Include the new or existing means of egress lighting and exit signs. (2018 sections 1008.3, 1013) 5. Sheet A1.030: Show the deck or balcony outside of the sliding doors in units A1, A2, A3. (2018 IBC section 107) Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 3/29/2024 8:24:19 PM 1. Plan Sheet M1.030 - Provide supply air duct sizes. Provide CFM quantities at all supply drops. - 2018 IBC Section [A]107.2.1Information on construction documents. 2. General - Provide Ventilation Calculation/Schedule. Show O/A to FCU - 2018 IMC Section Table 403.3.1.1. 3. General - Provide ComCheck Mechanical Compliance Certificate - 2018 IECC Section C403.2.3 HVAC equipment performance requirements 4. General - Provide locations of condensers and or refrigerant piping plans. - 2018 IBC Section [A]107.2.1Information on construction documents. Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 3/21/2024 4:01:29 PM 1. On sheet E2.0 and E2.1 some Unit’s Network box locations are missing a receptacle. 2. Could not locate Keynotes 7 and 11 on sheets E2.0 or E2.1 Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Approved Reason: Date Completed : 3/31/2024 3:20:23 PM First Plumbing Review: OK |
||
04/17/2024 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review PROJECT: TC-COM-0324-00439 1011 N TYNDALL AV. – UR-3 CONVERSION OF LEVEL 3 EXISTING FITNESS SPACE TO NINE RESIDENTIAL UNITS (1st Review) TRANSMITTAL DATE: April 17, 2024 Please resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the UR-3 zone (UDC 4.7.12). Mixed Use is an allowed use in the Main Gate UOD Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The Administrative Manual can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes-and-Plans/Zoning-Code#section-1. The proposed changes require a development package. If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov. |
||
04/15/2024 | Water - PDSD | REQUIRES RESUBMIT | Provide the size of the water meter serving the building and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. | ||
04/01/2024 | Fire New Construction | REVIEW COMPLETED | |||
03/16/2024 | PDSD Application Completeness | REVIEW COMPLETED |