Permit Number: TC-COM-0324-00437
Parcel: 129133350

Address:
2419 S PARK AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0324-00437
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/26/2024 Commercial Plumbing REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all comments were addressed.
1. The City of Tucson Commercial Submittal requirements state; All plans must be sealed and signed by an Architect or Engineer registered in the State of Arizona. Note. The term ‘building plans’ may refer to structural, electrical, plumbing, or any other trade regulated by the associated suite of codes adopted by the City of Tucson.
2. Provide a natural gas piping design sealed by an Arizona Registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. The design shall include the piping layout on a floor plan and a natural gas schematic showing the sizes, loads and developed lengths of each section of the branch piping. Reference: Sections 107.1 and 107.2.1, IBC 2018.



Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
03/11/2024 PDSD Application Completeness Express REVIEW COMPLETED