Permit Number: TC-COM-0324-00423
Parcel: 12709011M

Address:
333 N WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0324-00423
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2024 Site Zoning APPROVED
04/11/2024 Water - PDSD APPROVED
04/09/2024 Site Engineering NOT REQUIRED
04/23/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/23/2024 External Reviewers - Stantec REQUIRES RESUBMIT March 20, 2024
1st Review

Intertech Architectural Interiors
Attn: Wayne Swan
6089 East Grant Road


Re: RINCON RESEARCH
REMODEL (4TH FLOOR)

City of Tucson Permit Number: TC-COM-0324-00423
Stantec Project Number: 185215066
Stantec File Number: TUC-24-028

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B II-A 13,588 91 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

GENERAL COMMENTS

1. The nature of this proposed tenant space appears to be an office/testing laboratory based on the rooms with workbenches and eye wash stations. Are hazardous chemicals involved in the testing process? If so, please provide which ones and the quantities. We are trying to determine is control area will be needed. {I noticed the cabinet in the workshop. Is this a fire cabinet?} [Ref. IBC 2018 Sec. Table 307.1 & Sec. 414]


ARCHITECTURAL COMMENTS

Sheet G1

1. The code block indicates the plans designed to meet the 2016 NEC. Please revise this to reflect the 2017 NEC as adopted by the City of Tucson.

Sheet D1

1. Keynote 13 of the demolition plan keynotes is not located on the plan. Please indicate the location of keynote 13 on the demolition plan.

Sheet A1

1. Plans have conflicting information. Keynote 14 indicates that the sink and eye was station are to be future fixtures and only plumbing to be to be installed and capped but sheet P1 of the plumbing plans indicates the fixtures to be installed. Please clarify and coordinate.

Sheet A5

1. The detail indicated for drilling of the existing post-tensioned concrete is not stamped by an engineer for compliance. Please have the design reviewed by an engineer to verify structural compliance with proposed no drilling zones, concrete column clearance, and 8” core allowance. Please also clarify the elements of the detail. What does the tightly spaced hatches represent? The dimensions from the column indicate 30” but the description says a clearance of 36” from the column. Please clarify.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. Please provide energy conservation compliance reports for the new mechanical units indicated. [Ref. IECC 2018 C403.3.2]

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/01/2024 Fire New Construction REVIEW COMPLETED
03/13/2024 PDSD Application Completeness REVIEW COMPLETED