Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0324-00422
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/19/2024 Commercial Electrical REQUIRES RESUBMIT Permit Review TC-COM-0324-00422 (3357 N COUNTRY CLUB RD Unit:UNIT 18 TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. The 12-meter pack replacement can be on one permit, but each addressed unit must be listed on the provided plans. Provide an updated site plan showing each addressed unit associated with the meter pack.
2. You will need to submit an address change request through the TDC Portal and request that each addressed unit to be listed on the permit. See the TDC FAQ page for step-by-step instructions. https://www.tucsonaz.gov/Departments/Planning-Development-Services/Frequently-Asked-Questions/Tucson-Development-Center-Online-Instructions
3. Provide a complete line diagram, NEC 110.2, 2018 IBC 107.1.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/06/2024 PDSD Application Completeness Express REVIEW COMPLETED