Permit Number: TC-COM-0324-00416
Parcel: 12908018B

Address:
1747 E 23RD ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0324-00416
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/12/2024 Commercial Structural REQUIRES RESUBMIT TC-COM-0324-00416 (1747 E 23RD ST TUCSON, AZ 85713)
Certificate of Occupancy / C of O
Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. The use of this building appears to be Factory and not Storage as indicated in the Code Analysis Please revise. IBC 107,2,1
2. Please update all applicable areas of Code Analysis to the Occupancy classification of Factory F1 or F2. IBC 306.1
A. F1 if fabrication, finishing, manufacturing, packaging, assembly or processing of materials that are combustible or that use combustible products in the production process.
B.F2 if for the purpose of fabrication, manufacturing or processing of noncombustible materials. It is acceptable for noncombustible products to be packaged in a combustible material, provided that the fuel load contributed by the packaging is negligible when compared to the amount of noncombustible product.
3. Related to the above, please recalculate the occupant load with any change of Occupancy Group. IBC 1004.1 Additionally, update the plumbing fixture requirements based on the new occupant load factor. IBC 2901.1
4. Provide illumination for the means of egress, including the exit discharge per IBC 1008. Show compliance with the following:
A. The means of egress shall be illuminated at all times the building space is occupied.
B. The means of egress illumination level shall not be less than 1 foot-candle at the walking surface.
C. The means of egress illumination shall be supplied by backup power (consisting of storage batteries, unit equipment, or an on-site generator) for a duration of not less than 90 minutes. [IBC 1008.3]
5. Please amend plans to show the type and location of exit signs on the plans IBC 1013.1
6. Amend plans to provide Outdoor air calculations in accordance with IMC Chapter 4, if occupant load has increased from previous occupancy. [IEBC 1008]

Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
04/01/2024 Fire New Construction REQUIRES RESUBMIT -Explain why your are not considered a Factory per the definition. You state your assemble but you're applying for an S2 occupancy classification.
-Indicate the height of the shelves/racks.
-What type of products are being stored?
john.vincent@tucsonaz.gov
5203495581
04/09/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: TC-COM-0324-00416
1747 E 23RD ST. – I-1
C of O (2nd Review)

TRANSMITTAL: April 9, 2024

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the I-1 zone (UDC 4.7.29), Assembly, Precision Manufacturing use is a permitted use in the zones (UDC Table 4.8-5), subject to Use Specific Standards 4.9.5.C.2, .5, .6, .7, & .8 and 4.9.13.Q.

1. As you are proposing a change of use from commercial storage to assembly, precision manufacturing provide a vehicle parking space calculation the clearly demonstrated that the requirements of UDC Table 7.4.4-1 are met or clearly demonstrate that the requirements of UDC Article 3.3.3.H are met and provide all applicable documentation.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/12/2024 PDSD Application Completeness Express REVIEW COMPLETED