Permit Number: TC-COM-0324-00402
Parcel: 12810054A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0324-00402
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2024 Site Zoning APPROVED
04/15/2024 Water - PDSD APPROVED
04/05/2024 Site Engineering NOT REQUIRED
04/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/28/2024 External Reviewers - Stantec REQUIRES RESUBMIT March 18, 2024
1st Review

a23 Studios
Attn: Burak Bekat
711 E. 9th St.
Tucson, Arizona 85712

Re: FIJI WATER
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0324-00402
Stantec Project Number: 185215066
Stantec File Number: TUC-24-027

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 8,960 80 Yes No
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

Sheet A1.1

1. The occupant load totals at the designated exits only total to 60 occupants and the total occupant load is calculated at 80. Please adjust the exit totals to reflect the total occupant load. [Ref. IBC 2018 Sec. 1005]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please provide an electrical demolition plan for the proposed T.I.

Sheet E1.0

1. Please identify what loads are new on the panel schedule for Panel L4.

Sheet E2.0

1. Note 5 of the general notes indicates no new loads are to be added but it looks as though new loads are added due to the addition of a breakroom area and its associated appliances/receptacles and rooms created due to remodel. Please clarify.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/19/2024 Fire New Construction REVIEW COMPLETED
03/11/2024 PDSD Application Completeness REVIEW COMPLETED