Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2023 Commercial Electrical APPROVED
05/03/2023 Commercial Mechanical APPROVED
05/04/2023 Commercial Structural APPROVED
04/28/2023 Site Zoning APPROVED
04/19/2023 Site Engineering NOT REQUIRED
05/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/03/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Clarify the connected loads or input ratings for each appliance. Southwest Gas, the local gas utility, provides natural gas with an energy content of approximately 1,000 BTU per cubic foot. Reference: Section 402.1, IFGC 2018.
2. If the natural gas pipe sizes were not based on a maximum developed pipe length of 150 feet, state how the pipe size was determined. Reference: Sections 402.1 and 402.3, IFGC 2018.
3. Verify the minimum gas service pressure required for each of the appliances. Reference: Section 402.1, IFGC 2018.
4. Provide an automatic fuel shut off valve for the Type I hood, interlocked with the hood fire extinguishing system. Reference: Section 904.3.3, IBC 2018.
5. Clarify the routing of the vents for the grease interceptor. The vents appear to connect to the building drain. Reference Section 107.2.1, IBC 2018.
6. Show that each trap and trapped fixture has been vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2018.
04/14/2023 Fire New Construction REVIEW COMPLETED
04/05/2023 PDSD Application Completeness Express REVIEW COMPLETED