Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0323-00937
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/14/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. The branch serving the griddle and ACU-2 (127 CFH @ 100 feet) is undersized based on Table 402.4 (2), IFGC 2018. [Initial comment: If the natural gas pipe sizes were not based on a maximum developed pipe length of 150 feet, state how the pipe size was determined. Reference: Sections 402.1 and 402.3, IFGC 2018.] 2. Vents located inside must rise vertically to at least 6” above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2018. [Initial comment: Show that each trap and trapped fixture has been vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2018.] |
||
| 05/15/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |