Permit Number: TC-COM-0323-00937
Parcel: 10321029Y

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0323-00937
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/14/2023 Commercial Plumbing REQUIRES RESUBMIT 1. The branch serving the griddle and ACU-2 (127 CFH @ 100 feet) is undersized based on Table 402.4 (2), IFGC 2018. [Initial comment: If the natural gas pipe sizes were not based on a maximum developed pipe length of 150 feet, state how the pipe size was determined. Reference: Sections 402.1 and 402.3, IFGC 2018.]
2. Vents located inside must rise vertically to at least 6” above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2018. [Initial comment: Show that each trap and trapped fixture has been vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2018.]
05/15/2023 PDSD Application Completeness Express REVIEW COMPLETED