Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0323-00936
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/01/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Indicate the available fault current at the service and correlate with the new Panelboard. 2 Why do the electrical service line diagrams show all the feeders taped together in the gutter? 3 Provide a complete panel schedule including the identification of the panel and all the branch circuits and feeders. NEC 408.4. 4 Show all the electrical equipment on the line diagrams that are associated with the new electrical service that correlates with the equipment shown on the site plan. See ‘CALLOUTS’ notes. 5 Why does the ‘CONDUIT AND WIRING SCEDULE’ (plan sheet 3 and 4) show ‘(4) TYP 200A 3Ph CIRCUIT, P1 - 2-#8cu, 1#8cu, 1#10cu, ¾", 25% ? Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
| 04/04/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |