05/01/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Indicate the available fault current at the service and correlate with the new Panelboard.

2 Why do the electrical service line diagrams show all the feeders taped together in the gutter?

3 Provide a complete panel schedule including the identification of the panel and all the branch circuits and feeders. NEC 408.4.

4 Show all the electrical equipment on the line diagrams that are associated with the new electrical service that correlates with the equipment shown on the site plan. See ‘CALLOUTS’ notes.

5 Why does the ‘CONDUIT AND WIRING SCEDULE’ (plan sheet 3 and 4) show ‘(4) TYP 200A 3Ph CIRCUIT, P1 - 2-#8cu, 1#8cu, 1#10cu, ¾", 25% ?

Ref; 2018 IBC section 107.2.1, 2017 NEC