Permit Number: TC-COM-0323-00928
Parcel: 106041670

Address:
3327 N 1ST AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0323-00928
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2023 Commercial Electrical APPROVED
04/19/2023 Site Engineering NOT REQUIRED
05/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/01/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.
2. Footnote b on Table 403.3.1.1, IMC 2018 states that mechanical exhaust is required for the smoking lounge and no air from the smoking lounge may be recirculated to any other space. Reference: Section 403.2.1 (3), IMC 2018
05/01/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Correct the occupant load for the assembly area (1394 SF/15=93). Reference: Section 403.1, IPC 2018.
2. Provide the number of drinking fountains that complies with the requirements of Sections 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018.
3. Provide a service sink to comply with the requirements of Sections 2902.1 and 2902.5, IBC 2018.
05/01/2023 Commercial Structural REQUIRES RESUBMIT Please respond to the following:
1. Occupancy changed from B to A-2, the type of use also changed from Gym to Food Service.
2. Submit a complete set of drawings depicting what is being proposed.
3. Submit/show an exiting diagram on a floor plan. Please include with it the 2 required Exit that are located not less than half of the maximum overall diagonal dimension of the building IBC 1006.3.2.
4. Show all the actual physical equipment and furniture on the plan.
5. Food preparation area must show all equipment, show hood location, submit plumbing drawings, electrical, mechanical for the entire establishment (not just the prep area, if they are existing...identify them as existing). Please submit to the Health Department.
6. Assuming that the 96 occupant load shown on your initial submission is correct, show/identify on your site plan the parking stalls per UDC 7.4.4 that will be used by this space to include the required handicap spaces as well as the striped accessible route, required bicycle rack, identify the delivery/unloading space, etc.
7. At 96 occupant load, please accurately re-do your Code Analysis to include the plumbing fixture requirements based on IBC Table 2902.1, reflect on your drawing the required number of fixtures.
8. Please re-submit.
04/21/2023 Fire New Construction REQUIRES RESUBMIT Provide exits in accordance with IFC 20118, 1007.1.1
Questions: patricia.shelton@tucsonaz.gov / 520.837.7082
05/05/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0323-00928
3327 N. 1st St. – C-2
TI – Food Service w/Accessory Use Retail (1st Review)

TRANSMITTAL: May 5, 2023, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in C-2 zone (UDC 4.7.2), Food Service is a permitted use in the zone, subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

1. Based on discussions with staff, Elisa Hamblin, Zoning Administrator, this use is considered food service with an accessory use of general merchandise sales and shall be parked at the food service requirement of 1 space per 100 sq. ft. of gross floor area. Provide a vehicle parking space calculation that clearly demonstrates that the entire site, parcels 106-04-1670 & 106-04-1680, either meet the requirements of a shopping center, see UDC Article 11.3.9.C.3 and UDC Table 7.4.4-1: MINIMUM NUMBER OF MOTOR VEHICLE SPACES REQUIRED, RETAIL TRADE USE GROUP, Shopping Center, 1 space per 300 sq. ft. GFA, or the requirements of a mixed use, see UDC Article 7.4.4.A.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/05/2023 PDSD Application Completeness Express REVIEW COMPLETED