Permit Number: TC-COM-0323-00926
Parcel: 12710017D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0323-00926
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2023 Site Zoning APPROVED
04/19/2023 Site Engineering NOT REQUIRED
04/21/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
04/21/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0323-00926


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Refer to Mechanical Drawings M1.0 and M2.0. The Drawing M1.0 shows a condenser unit is being added to the existing roof of the building. The Drawing M2.0 shows the weight of the condenser unit as 250 pounds. Verify the adequacy of the existing roof to support the additional load of the condenser unit. Submit Structural Calculations supporting your response.
2. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Denied
1. Sheet TS-1: The occupant load for business are of the project is calculated incorrectly. Provide a corrected occupant load calculation in accordance with Table 1004.5.
2. Sheet TS-1: It appears that the seating in the waiting room is not fixed seating. This area is considered an assembly area. Provide a corrected occupant load calculation in accordance with Table 1004.5.
3. Sheet A1.0 and A1.1: The corridor walls are required to be rated. Provide a listed assembly that is rated properly for the corridor walls in accordance with Table 1020.1.
4. Sheet A1.0 and A1.1: The door in the corridor walls are not rated properly. Provide properly rated doors in accordance with Table 716.1(2).


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Plan pages P1.1 , P1.2, & P3.1 missing the required High/Low drinking fountain as shown on A1.1 -IPC 403.1
2). Add Vacuum & compressed air piping materials to plan page MP1.0 -NFPA99 Chapter 15
3). The med gas closet doors on plan pages P1.3 & A3.0 need to have their doors labeled according to NFPA99 15.4.2.2.8
4). Vacuum exhaust piping on plan page P2.2 can't be CPVC -NFPA99 5.1.3.7.7.6
5). Med Gas storage room on plan pages M1.0 & P1.3 need to be ventilated according to NFPA99 SECTIONS 5.1.3.3.3.1, 9.3.6.5.2, 9.3.6.5.2.5
6). This occupancy type & load B 71 requires 4 toilets, only 3 shown - IPC 403.1, update all affected pages.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/20/2023 Fire New Construction REVIEW COMPLETED
04/05/2023 PDSD Application Completeness REVIEW COMPLETED