Permit Number: TC-COM-0323-00926
Parcel: 12710017D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0323-00926
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/31/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0323-00926

GENERAL:
⦁ Provide written responses to all review comments.
⦁ Provide a complete plan set.
⦁ Provide additional documents as requested by review staff.

Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 5/31/2023 7:48:45 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/19/2023 10:31:00 AM

Mechanical(M) Reviewer (from previous submittal TUC9227001.040523)
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 4/8/2023 5:30:11 PM
Approved/subject to field approval

Electrical(E) Reviewer (from previous submittal TUC9227001.040523)
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 4/18/2023 5:23:06 PM

Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 5/28/2023 8:28:42 AM
SecondPlumbing Review:
1). OK
2). OK
3). SAME-The med gas closet doors on plan pages P1.3 & A3.0 need to have their doors labeled according to NFPA99 15.4.2.2.8 ** No change on A3.0 as stated in response**
4). SAME-Vacuum exhaust piping on plan page P2.2 can't be CPVC -NFPA99 5.1.3.7.7.6 ** The vacuum exhaust piping is not listed in NFPA99 Chapter 15 ( dental) , provide vacuum manufacture specs showing use of CPVC is allowed**
5). SAME-Med Gas storage room on plan pages M1.0 & P1.3 need to be ventilated according to NFPA99 SECTIONS 5.1.3.3.3.1, 9.3.6.5.2, 9.3.6.5.2.5 ** Plan page M1.0 does not notate or illustrate any med gas closet ventilation, as stated in comment response**
6). OK
05/16/2023 PDSD Application Completeness REVIEW COMPLETED