Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0323-00926
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/31/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/31/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: TC-COM-0323-00926 GENERAL: ⦁ Provide written responses to all review comments. ⦁ Provide a complete plan set. ⦁ Provide additional documents as requested by review staff. Structural(S) Reviewer Daljit Benipal dbenipal@safebuilt.com Conditionally Approved Reason: Date Completed : 5/31/2023 7:48:45 AM NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 5/19/2023 10:31:00 AM Mechanical(M) Reviewer (from previous submittal TUC9227001.040523) Neil Samaan nsamaan@safebuilt.com Conditionally Approved Reason: Date Completed : 4/8/2023 5:30:11 PM Approved/subject to field approval Electrical(E) Reviewer (from previous submittal TUC9227001.040523) Ron Ross rross@safebuilt.com Approved Reason: Date Completed : 4/18/2023 5:23:06 PM Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 5/28/2023 8:28:42 AM SecondPlumbing Review: 1). OK 2). OK 3). SAME-The med gas closet doors on plan pages P1.3 & A3.0 need to have their doors labeled according to NFPA99 15.4.2.2.8 ** No change on A3.0 as stated in response** 4). SAME-Vacuum exhaust piping on plan page P2.2 can't be CPVC -NFPA99 5.1.3.7.7.6 ** The vacuum exhaust piping is not listed in NFPA99 Chapter 15 ( dental) , provide vacuum manufacture specs showing use of CPVC is allowed** 5). SAME-Med Gas storage room on plan pages M1.0 & P1.3 need to be ventilated according to NFPA99 SECTIONS 5.1.3.3.3.1, 9.3.6.5.2, 9.3.6.5.2.5 ** Plan page M1.0 does not notate or illustrate any med gas closet ventilation, as stated in comment response** 6). OK |
||
05/16/2023 | PDSD Application Completeness | REVIEW COMPLETED |