Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0323-00914
Parcel: 134251990

Address:
7025 E 21ST ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0323-00914
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2023 Commercial Plumbing APPROVED
06/22/2023 Commercial Mechanical NOT REQUIRED
06/08/2023 Site Engineering NOT REQUIRED
06/27/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/26/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide a specification for the new ‘EXIT Signs with Lights’ and verify compliance with 2018 IBC section 1008.

2 Provide branch wiring methods for the ‘New Exit Signs with Lights’.

Ref; 2018 IBC section 107.2.1, 1008, and 2017 NEC.
06/27/2023 Commercial Structural REQUIRES RESUBMIT Please respond to the following: 1. Can the City assume to use 131 as the Occupant Load and not 169 as shown in the Minimum Plumbing Table. 2. Please confirm that the Lighted Sign is attached with the Emergency Light w/ Rechargeable Battery Backup as shown on your drawing. Notate this on the plan. 3. Please confirm that the ramps shown on the floor plan are ANSI A117 compliant with maximum slope of 1 to 12. If so, please notate it on the plan where ramps are shown. 4. Are doors ANSI compliant and able to accommodate wheel chairs. If so, please notate the door dimensions right on the plan. 5. Install an ANSI compliant ramp at the raised platform/stage. 6. Is Alarm already exists on this facility. If so, please notate it on the plan. 7. Include a statement as part of your code analysis as to how the facility handles any persons receiving custodial care who require limited verbal or physical assistance responding to an emergency situation to complete building evacuation and self preservation. Specify Condition 1 or Condition 2 per IBC 310. 8. Please resubmit.
06/06/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0523-00914
7025 E. 21st St – C-2
TI – Medical Service Outpatient (1st Review)

TRANSMITTAL: June 05, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in C-2 Zone (UDC 4.7.21). Medical Services, Outpatient, excluding blood donor centers, is an allowed use in the zone, (UDC Table 4.8-4), subject to Use Specific Standard 4.9.4.O.2 and 4.9.13.P.

1. As this is a change of use either provide a vehicle parking space calculation that clearly shows the number required & provided and that the required is met or review UDC Article 3.3.3.H and provide the required documents per UDC Article 3.3.3.H.9.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/07/2023 Fire New Construction REVIEW COMPLETED
05/24/2023 PDSD Application Completeness Express REVIEW COMPLETED