Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0323-00907
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/08/2023 Commercial Mechanical REQUIRES RESUBMIT The mechanical drawings are still using the 2012 edition of the IECC instead of the 2018 edition of the IECC.
08/08/2023 Commercial Plumbing REQUIRES RESUBMIT Comment not resolved. The specified water heater has an atmospheric vent, it is not a condensing water heater and it does not use a concentric intake and flue (details 9/M501 and 8/P501). If you wish to use a direct vent water heater, revise the water heater specifications appropriately. Install the water heater per the manufacturer’s instructions. [Second comment: The specified water heater is not a condensing water heater and may not use a PVC flue. Show the installation of the water heater in conformance with the manufacturer’s installation instructions. Note: the natural gas input is 40 MBH.] [Initial comment: The specified water heater was discontinued in 2012. Provide a specification for a water heater that can be installed. Verify that the installation of the specified water heater conforms to the manufacturer’s installation instructions. Reference: Section 107.2.1, IBC 2018. ]
07/19/2023 PDSD Application Completeness Express REVIEW COMPLETED