Permit Number: TC-COM-0323-00906
Parcel: 10511061R

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0323-00906
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2023 Site Zoning APPROVED
04/19/2023 Site Engineering NOT REQUIRED
04/19/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
04/19/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0323-00906

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditinally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Denied
E-120 SECOND FLOOR DEMOLITION PLAN: Could not locate Keynote #5.
E-310 FIRST FLOOR POWER PLAN: Need to provide an interior lighting Comcheck to show IECC compliance.
E-602 PANEL SCHEDULES: 125-amp Bus rating for LP1 section 2 is not sufficient for panel. Needs to be fully rated at 400 amps when connected with feed thru lugs. As Panel LP1 is new, it also needs to call out the minimum KAIC rating required.


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). The replaced high/low drinking fountain location on plan page P-210 doesn't correlate with plan pages A-031 & A-210. Plan pages need to correlate -IPC 106.3.1 ( If drinking is relocating show plumbing illustrations)
2). Illustrate High/Low drinking fountain same as A-031 & A-210 - IPC 410.3



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/14/2023 Fire New Construction REVIEW COMPLETED
04/03/2023 PDSD Application Completeness REVIEW COMPLETED