Permit Number: TC-COM-0323-00830
Parcel: 141367940

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0323-00830
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2024 Site Engineering APPROVED
05/15/2024 Site Zoning APPROVED
05/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/23/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 4/19/2024 11:13:14 AM
1. S2.3 - MISSING BEAM SIZE: The revised Common Area High Roof Framing Plan has replaced Beam Type "B1" with Beam "B6" over the plan-north and plan-south lobby entrances. Beam Type "B6" is not defined on the Beam Schedule on Sheet S1.9, last submitted as part of Delta 6, dated 8/14/23. Please provide a new Beam
Schedule or call out the revised beam size on plan.

2. S2.3 - MISSING DETAIL: At the new beam described in Comment #1, the framing plan also includes section cuts for Detail 237 at each end of the beam. Detail 237 does not appear on Sheet S4.3, last submitted as part of Delta 7, dated 8/28/23. Please provide an updated Sheet S4.3 with the missing detail included or revise the section cut on plan.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 4/18/2024 4:26:41 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 4/18/2024 3:37:43 PM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 4/21/2024 6:15:34 PM
Revised plan Plumbing Review: OK
05/13/2024 Fire New Construction REVIEW COMPLETED
04/17/2024 PDSD Application Completeness REVIEW COMPLETED