Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0323-00826
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/31/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/31/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan revie comments and provide a written response. 1. As requested. Identify the building that the PV arrays are installed, on the site plans. Also identify the building electrical service on the line diagrams. 2. As well as bonding to the Building Grounding Electrode System that the PV array is located NEC 690.47. The equipment ground must be maintained with the PV output conductors from Building #1 to Building #2. NEC 690.43(A)(B)(C). Ref; 2018 IBC section 107.2.1, 2017 NEC. City of Tucson Commercial Electrical Plan Submittal Requirements. |
||
| 07/12/2023 | Fire New Construction | REQUIRES RESUBMIT | Provide perimeter pathways in accordance with IFC 2018, 1204.3.1 | ||
| 06/28/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |