Permit Number: TC-COM-0323-00822
Parcel: 13415001F

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0323-00822
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2023 Site Zoning APPROVED
04/11/2023 Site Engineering NOT REQUIRED
04/12/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
04/03/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0323-00822

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1) The patio area is shown differently on the plans. Need the structural plans and elevation views.
2) Show the door sizes of all of the new, existing, and relocated doors.
3) The toilet room doors do not have the required maneuvering clearances per ICC A117.1 section 404.2.3 and 404.2.3.5.
4) The plumbing and HVAC drawings do not match the design shown on the floor plans. The washer and dryer are in a small closet along with a mop sink.
5) Detail location of HVAC equipment above ceiling, drain pans, condensate drains, support, etc. above the new ceiling (elevation section).


BUILDING REVIEW COMMENTS:
Denied
1) The occupancy load is to be calculated based on the uses and purpose of the individual areas or rooms using Table 1004.5.
2) The patio area is shown differently on the plans. Need the structural plans and elevation views.
3) Show the door sizes of all of the new, existing, and relocated doors.
4) The toilet room doors do not have the required maneuvering clearances per ICC A117.1 section 404.2.3 and 404.2.3.5.
5) Include the range and range hood spec sheets.
6) Include the new or existing exit discharge lighting per Sections 1008.2 and 1008.3
7) Need a COMcheck energy compliance report.
8) Detail location of HVAC equipment above ceiling, drain pans, condensate drains, support, etc. above the new ceiling (elevation section).


MECHANICAL REVIEW COMMENTS:
Denied
1) Include the range and range hood spec sheets.
2) The plumbing and HVAC drawings do not match the design shown on the floor plans. The washer and dryer are in a small closet along with a mop sink.
3) Detail location of HVAC equipment above ceiling, drain pans, condensate drains, support, etc. above the new ceiling (elevation section).
4) Provide gas piping details and calculations if applicable.


ELECTRICAL REVIEW COMMENTS
Denied
1) Include the range and range hood spec sheets.
2) Include the new or existing exit discharge lighting per Sections 1008.2 and 1008.3
3) Need a COMcheck energy compliance report.
4) Electrical plans do not show the water heater power and disconnect, toilet room exhaust fan power, HVAC equipment power, range hood power, etc. Show the location of the panel supplying this unit and equipment.
5) The FACP does not have the required safe workspace per Section 110.26.
6) Correctly label the panel with the specific spaces or equipment being supplied by the circuit


PLUMBING REVIEW COMMENTS:
Denied
1) The occupancy load is to be calculated based on the uses and purpose of the individual areas or rooms using Table 1004.5.
2) The toilet room doors do not have the required maneuvering clearances per ICC A117.1 section 404.2.3 and 404.2.3.5.
3) The plumbing and HVAC drawings do not match the design shown on the floor plans. The washer and dryer are in a small closet along with a mop sink.
4) The mop sink DWV and supply piping along with the drain pans and condensate drains need to be shown.
5) Provide gas piping details and calculations if applicable


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/12/2023 Fire New Construction REVIEW COMPLETED
03/17/2023 PDSD Application Completeness REVIEW COMPLETED