Permit Number: TC-COM-0323-00822
Parcel: 13415001F

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0323-00822
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/30/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0323-00822

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 6/29/2023 12:58:15 PM
Please see the building review comments. No structural revisions needed at this time.


Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 6/29/2023 12:55:49 PM
1) Electrical plans do not show the toilet room exhaust fan power. Toilet room fans are shown on the lighting demo plans and are not shown on the new lighting plans which are controlled by a new occupancy sensor but no notes for the exhaust fans.
2) Correctly label the panel with the specific spaces or equipment being supplied by the new or existing circuit on page E4.
Numerous circuits are generically labeled for the prior use. Sections 110.22 and 408.4 require the breakers are labeled for the current space or equipment supplied by the breaker such as toilet rooms, activity area, TV room, office, quiet room, etc. light and receptacle circuits.
3) Show location of the condensate disposal for the water heater and HVAC equipment drain pans.


Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 6/29/2023 12:56:59 PM
Please see the building review comments.


Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 6/29/2023 12:56:33 PM
Please see the building review comments.


Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 6/29/2023 12:57:25 PM
Please see the building review comments.
06/28/2023 PDSD Application Completeness REVIEW COMPLETED