Permit Number: TC-COM-0323-00816
Parcel: 13215001C

Address:
705 E AJO WY

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0323-00816
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2023 Commercial Plumbing NOT REQUIRED
03/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/22/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide listed and labeled appliances. Reference: Sections 301.7 and 1101.2, IMC 2018.
2. Show that the proposed appliances meet the mandatory refrigeration system efficiency requirements for walk-in coolers (AWEF). Reference: Section C403.10.2.1, IECC 2018.
3. The proposed refrigerant, R-454C, has a 4 rating for fire (NFPA 704) while R-22 has a 0 rating for fire. With what fire suppression system is the walk-in cooler equipped? Reference: Section 107.2.1, IBC 2018.
03/17/2023 PDSD Application Completeness Express REVIEW COMPLETED