Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0323-00816
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/22/2023 | Commercial Plumbing | NOT REQUIRED | |||
03/22/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/22/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide listed and labeled appliances. Reference: Sections 301.7 and 1101.2, IMC 2018. 2. Show that the proposed appliances meet the mandatory refrigeration system efficiency requirements for walk-in coolers (AWEF). Reference: Section C403.10.2.1, IECC 2018. 3. The proposed refrigerant, R-454C, has a 4 rating for fire (NFPA 704) while R-22 has a 0 rating for fire. With what fire suppression system is the walk-in cooler equipped? Reference: Section 107.2.1, IBC 2018. |
||
03/17/2023 | PDSD Application Completeness | REVIEW COMPLETED |