Permit Number: TC-COM-0323-00813
Parcel: 12008243A

Address:
4710 S 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.4

Permit Number - TC-COM-0323-00813
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/14/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
The comment response submitted did not address the previous plan review comments.
1. Previous comment; Please address the electrical plan review comments and provide a written response Provide a detailed description of the scope of work. Is this a new additional service to be installed on a existing building? Is this a service upgrade to replace an existing service?
2. Provide an electrical site plan showing all electrical services and locations, ratings.
3. The Registrant seal and other lettering and notes are not legible. Please re-submit using a PDF format that is legible.
Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
08/09/2023 PDSD Application Completeness Express REVIEW COMPLETED