Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.5
Permit Number - TC-COM-0323-00813
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.5
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/17/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/17/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The previous electrical plan review comments are not completely addressed. 1 The registrant seal is not legible. 2 The wording on the plans is not clear, especially when trying to zoom in (blurry). 3 Is the new electrical service going to be installed in the same location as the existing service. 4 Is this the only electrical service on the building? If not, provide compliance with NEC art 230.2. 5 The response letter is hard to understand. Please have the Engineer of record write the response letter or someone proficient in the English language. 6 Re-submit plans using a PDF format that is clear. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
| 08/16/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |