Permit Number: TC-COM-0323-00813
Parcel: 12008243A

Address:
4710 S 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.5

Permit Number - TC-COM-0323-00813
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/17/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The previous electrical plan review comments are not completely addressed.

1 The registrant seal is not legible.

2 The wording on the plans is not clear, especially when trying to zoom in (blurry).

3 Is the new electrical service going to be installed in the same location as the existing service.

4 Is this the only electrical service on the building? If not, provide compliance with NEC art 230.2.

5 The response letter is hard to understand. Please have the Engineer of record write the response letter or someone proficient in the English language.

6 Re-submit plans using a PDF format that is clear.

Ref; 2018 IBC section 107.2.1, 2017 NEC
08/16/2023 PDSD Application Completeness Express REVIEW COMPLETED