Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0323-00768
Parcel: 11506128A

Address:
101 W VENTURA ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0323-00768
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2023 Site Zoning APPROVED
07/06/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/06/2023 Commercial Building REQUIRES RESUBMIT Please respond to the following:
1. Is a Fire Alarm already exist, if so please show it on your drawings. If not, please propose to install it, it is required
2. You are proposing to use the B Occupancy. Unfortunately, this will not fully cover the use that you are proposing and the needs of the individuals attending your services. Upon further analysis, we looked at E Occupancy...however, it too is not sufficient. We looked at I-1, however it allows 16 maximum clients (you are proposing 18). Our analysis points to I-4 which allows more than 5 of any age who receive custodial care for fewer than 24 hours per day as an Adult Day Care. Please do take a deep dive into this and do your own analysis to make sure that you are satisfactory with using I-4 and that it does give you all that is needed for this facility. Should you agree to use I-4 please correct your drawings to reflect this.
3. Please clarify your building square footage. You show it as 2642 sf within the code analysis, 1502 + 1134 sf = 2636 on your egress plan & you show 3300 on youur application.
4. Please submit a copy of the draft of the Operator's License Application with the State.
5. Please show the emergency lights locations.
6. You are proposing to do quite some work fon this facility. Please submit a complete set if drawings to include architectural, mechanical, plumbing and electrical.
7. Please resubmit.
07/03/2023 Water - PDSD REQUIRES RESUBMIT Show the location of the water meter, backflow preventer, and the water service pipe on a site plan. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018.
06/27/2023 Fire New Construction REVIEW COMPLETED
06/02/2023 PDSD Application Completeness Express REVIEW COMPLETED