Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0323-00766
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/13/2023 | Site Zoning | APPROVED | |||
07/26/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
07/20/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Daljit Benipal dbenipal@safebuilt.com Denied Reason: Date Completed : 7/18/2023 2:58:06 PM 1. Verify if the new addition has new roof. If it does, provide Structural Drawings and details including Structural Calculations. Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 7/18/2023 5:28:17 PM Electrical(E) Reviewer Ron Ross rross@safebuilt.com Conditionally Approved Reason: Date Completed : 7/18/2023 6:18:42 PM 2nd Electrical Review By: Ron Ross PE E5.1 Panel Schedule HB should have a 400 amp MCB to match with what is shown on One-Line. |
||
07/26/2023 | Fire New Construction | REVIEW COMPLETED | |||
07/07/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |