Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0323-00756
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/11/2023 | Commercial Electrical | APPROVED | |||
04/25/2023 | Commercial Structural | APPROVED | |||
03/21/2023 | Site Zoning | APPROVED | |||
04/04/2023 | Site Engineering | NOT REQUIRED | |||
04/25/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
04/17/2023 | Commercial Mechanical | REQUIRES RESUBMIT | Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). The minimum exhaust flow rate is 50 CFM per water closet if the exhaust is continuous. Reference: Sections 403.2.1 (4) and 403.3.1.1, and Table 403.3.1.1, IMC 2018. | ||
04/17/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Revise the plumbing plans to show the extent of the plumbing work in the break room (i.e. the automatic dishwasher and refrigerator). Reference: Section 17.2.1, IBC 2018. 2. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. |
||
04/25/2023 | Fire New Construction | REVIEW COMPLETED | |||
03/13/2023 | PDSD Application Completeness | REVIEW COMPLETED |