Permit Number: TC-COM-0323-00756
Parcel: 113052560

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0323-00756
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2023 Commercial Electrical APPROVED
04/25/2023 Commercial Structural APPROVED
03/21/2023 Site Zoning APPROVED
04/04/2023 Site Engineering NOT REQUIRED
04/25/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
04/17/2023 Commercial Mechanical REQUIRES RESUBMIT Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). The minimum exhaust flow rate is 50 CFM per water closet if the exhaust is continuous. Reference: Sections 403.2.1 (4) and 403.3.1.1, and Table 403.3.1.1, IMC 2018.
04/17/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Revise the plumbing plans to show the extent of the plumbing work in the break room (i.e. the automatic dishwasher and refrigerator). Reference: Section 17.2.1, IBC 2018.
2. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
04/25/2023 Fire New Construction REVIEW COMPLETED
03/13/2023 PDSD Application Completeness REVIEW COMPLETED