Permit Number: TC-COM-0323-00742
Parcel: 12713078B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0323-00742
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2023 Commercial Plumbing APPROVED
07/21/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/17/2023 Commercial Mechanical REQUIRES RESUBMIT The exhaust fan, EF-1, is scheduled to move 500 CFM but the balancing data on the mechanical floor plan only shows 400 CFM of exhaust. [Initial comment: A restaurant has different ventilation and exhaust requirements than a karate studio (ATA Black Belt Academy). Provide a mechanical design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2018.]
07/21/2023 Commercial Structural REQUIRES RESUBMIT Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.

Provide a complete Code Analysis to include:
1. Occupancy Classification/Group (this should be A-2)
2. Confirm that Fire Sprinkler exist
3. Re-verify the allowable area per IBC table 506.2
4. Provide a detailed calculation of the occupant load, provide a tally for each area/space leading to the total occupant load.
5. Provide the calculation in determining the water closet and lavatories required based on the occupant load per IBC table 2902.1
6. Provide the calculation for egress sizing per IBC 1005.
7. Are emergency light with battery back up installed.


Correct all the building codes year.


On your Site Plan, identify the location of the bicycle rack(s).


Indicate which equipments are NSF compliance.


Egress Plan:
Show the dimension of the overall diagonal of the restaurant per IBC 1007. Provide the distance between required exits. NOTE: egress shall not pass through kitchen, storage or closet per IBC 1016, unless the space is configured to allow safe passage.


ANSI A117 accessible wheelchair counter tops for employees and customers (show/label this on your plan). Wheelchair accessible tables for customers.

Please re-submit
07/07/2023 Fire New Construction REQUIRES RESUBMIT -Provide an occupancy group in the code analysis.
-Provide an occupant load in the code analysis.
-Your code analysis states 2 exits are required. If true, based on occupant loac, the rear door cannot be used as an exit as it exits through a storage area. IFC 1016 #5 with exceptions.
-The two front "exit" doors are not spaced accordingly if two exits are required. IFC Section 1007.
You will need to calculate your occupant load based on your occupancy type. This will determine the number of exits required.

john.vincent@tucsonaz.gov
5203495581
06/20/2023 PDSD Application Completeness REVIEW COMPLETED