Permit Number: TC-COM-0323-00733
Parcel: 137040540

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.6

Permit Number - TC-COM-0323-00733
Review Name: COMMERCIAL REVIEW - FULL v.6
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2026 Commercial Building Standard APPROVED Building (B) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 1/28/2026
The plans are approved. Subject to the field inspector’s approval.
01/28/2026 Commercial Electrical Standard APPROVED Electrical (E) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 1/28/2026
The plans are approved. Subject to the field inspector’s approval.
01/28/2026 Commercial Mechanical Standard APPROVED Mechanical (M) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 1/28/2026
The plans are approved. Subject to the field inspector’s approval.
01/28/2026 Commercial Plumbing Standard APPROVED Plumbing (P) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 1/28/2026
The plans are approved. Subject to the field inspector’s approval.
02/19/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/17/2026 Fire New Construction Standard REQUIRES RESUBMIT Cover sheet states fire sprinklers as a deferred submittal, however, sheet x1.1 in the code analysis states no fire sprinklers. Please make corrections. If not sprinklered, notes will be added stating this building is not for tire storage.
john.vincent@tucsonaz.gov
5203495581
02/19/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Krista Hansen
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-COM-0323-00733 - TD-DEV-0623-00273
5318 S NOGALES HY – C-2
Building Addition (4th Review)

TRANSMITTAL DATE: 2/19/2026


This site is zoned C-2 (UDC Section 4.7.21).


Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.


01. Previous Comment 1 – Per UDC Table 6.3-4.A, C-2 Zone, a Nonresidential Use adjacent to a Residential Zone requires a minimum setback of 1½(H) = Height of the proposed exterior building wall. Based on a wall height of 16’-0” the required perimeter yard setback from the proposed addition to the west property line is 24’-0” as measured from the midpoint of the proposed structure (UDC Article 6.4.5.B.5 and Figure 6.4.5-A). The associated Development Package (TD-DEV-0623-00273) shows a proposed setback of 16’-3” to the west property line. A Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration.

**Follow-up to Previous Comment 1 – The comment response letter states that the applicant applied for a DDO; however, there is no record of a DDO application. This DDO shall be approved prior to approval of this permit and should have been approved prior to the approval of the DP (TD-DEV-0623-00273). Please contact Mark Castro at Mark.Castro@tucsonaz.gov prior to applying for the DDO.


For questions regarding Zoning comments, please contact me at: Krista.Hansen@tucsonaz.gov
01/26/2026 PDSD Application Completeness Express REVIEW COMPLETED