Permit Number: TC-COM-0323-00733
Parcel: 137040540

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0323-00733
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/26/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0323-00733

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 5/25/2023 11:12:18 AM
See building review comments.


Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 5/25/2023 11:11:40 AM
No revisions have been made.
Unable to complete the review - insufficient plans. Please submit a complete set of plan pages (including MEP) in the same file. The files submitted have multiple duplicate copies and different designs shown on pages mixed in 3 files.
All plans need to be sealed by an engineer or architect. All pages need to be drawn to scale and consistent design among pages including the site plan.
Construction drawings need to include occupancy classification, occupant load calculations, Risk Category, construction type, allowed vs actual area, height, and stories, means of egress details, emergency lighting, exit signs, accessibility details, MEP, COMcheck, etc. of the new and existing buildings.
Include footing plans with section view showing width and depth.
06/02/2023 Fire New Construction REQUIRES RESUBMIT Address SAFEBuilt comments. Questions: patricia.shelton@tucsonaz.gov
06/05/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
06/02/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: TC-COM-0323-00733
5318 South Nogales Highway – C-2
Steel structure with restrooms (2nd Review)

TRANSMITTAL DATE: June 02, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. This comment was not addressed. Per Tucson Unified Development Code (UDC) Section 3.3.3.G.2.c, as you are proposing building or structure additions on a property developed with a non-residential use, a development package in accordance with Administrative Manual Section 2-06 is required to be approved prior to Zoning approval of this building permit. The development package is a separate submittal and shall be applied for under application type “Development Package” through the Tucson Development Center Online.

If you have any questions about this transmittal, please contact Nicholas Martell at Nicholas.Martell@tucsonaz.gov.
05/22/2023 PDSD Application Completeness Express REVIEW COMPLETED