Permit Number: TC-COM-0226-00273
Parcel: 125101470

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0226-00273
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2026 Commercial Electrical Standard APPROVED
05/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/11/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00273
ADDRESS/PARCEL: 3501 E BROADWAY BL TUCSON, AZ 85716
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Previous comment not addressed. A reduced pressure backflow preventer is required in place of the double check valve backflow preventer shown. Please also revise the plans to reference Detail SD-1802 instead of Detail SD-1805. [Previous comment - Reduced pressure backflow prevention assemblies (instead of double check valve assemblies) are required to be installed directly after the water meter for buildings that have chemicals, cleaning agents, or other contaminants that may come in direct contact with water. (see also Tucson Water Standard Detail 1802). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf ]
a. Per Section 27-75 (a) (15) of Article V, a reduced pressure principle assembly (RPA) is required for any premises on which chemicals, oils, solvents, pesticides, disinfectants, cleaning agents, acids or other pollutants and/or contaminants are handled in a manner by which they may come in direct contact with water, or there is evidence of the potential to contact water.
04/21/2026 PDSD Application Completeness Express REVIEW COMPLETED