Permit Number: TC-COM-0226-00273
Parcel: 125101470

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0226-00273
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2026 Commercial Building Standard NOT REQUIRED
03/24/2026 Fire New Construction Standard NOT REQUIRED
03/19/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
03/03/2026 Site Engineering Standard NOT REQUIRED
03/23/2026 Site Zoning Standard NOT REQUIRED
04/08/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/20/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0226-00273 (3501 E BROADWAY BL TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide electrical plans for the proposed scope of work, prepared by an Arizona Registered Electrical Engineer, IBC 107.5
a. Include the conductor sizes and types, conduit sizes, transformer ratings, etc.
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2023 NEC 110.24.
3. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2023 NEC 110.10.
04/08/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00273
ADDRESS/PARCEL: 3501 E BROADWAY BL TUCSON, AZ 85716
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide the size of the backflow preventer associated with the water meter, and the total water demand that will be served by the new 1” water meter. Reference: Section 107.2.1, IBC 2024
2. Reduced pressure backflow prevention assemblies (instead of double check valve assemblies) are required to be installed directly after the water meter for buildings that have chemicals, cleaning agents, or other contaminants that may come in direct contact with water. (see also Tucson Water Standard Detail 1802). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf .
03/02/2026 PDSD Application Completeness Express REVIEW COMPLETED