Permit Number: TC-COM-0226-00260
Parcel: 11007414J

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0226-00260
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2026 Commercial Electrical APPROVED
03/12/2026 Water - PDSD APPROVED
02/27/2026 Site Engineering NOT REQUIRED
03/13/2026 Site Zoning NOT REQUIRED
03/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/27/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding this review, please contact the team at PDSD-Permits@tucsonaz.gov

Parcel/addressing issue. The site plan shows to be creating a new Unit 105. The location does not have this unit attached to the address. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and add the unit numbers. After address/units have been added or verified you'll need to submit an address change request to update this record in the sub records tab.
03/16/2026 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00260
ADDRESS/PARCEL: (3901 E GRANT RD Unit:UNIT 103 TUCSON, AZ 85712)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. CERTIFICATE OF OCCUPANCY
a. Subdividing the existing space effectively invalidates the existing Certificate of Occupancy.
i. Since the title block of the drawing indicates suite 103, this building permit will be used for this suite.
1. The City is assuming that a new Certificate of Occupancy is sought for suite 103.
2. Please confirm.
ii. A separate Certificate of Occupancy is required for suite 105.
1. Is the C of O is sought for suite 105.
2. Please apply for a separate building permit.
2. NEW DEMISING WALL
a. Please provide demising wall detail drawing at the bottom/floor.
b. Please provide detail drawings at the top showing demising wall terminates at the bottom of the roof deck.
c. Please ensure to indicate type x gyp bd is used.
d. Please ensure that the 1 hour rated demising wall are also applied on the wall between restrooms. Please provide the wall detail drawing illustrating this.
3. WATER DISPENSER
a. Where the Building and Plumbing Codes require a drinking fountain, the City of Tucson will accept point of use water dispenser in lieu of the classically recognized drinking fountain.
b. The water dispenser must be listed and labeled in accordance with the Code.
c. The water dispenser must be connected to a permanent supply of potable water.
d. The water supply must be indicated on the plans and installed per code.
e. A clear floor space shall be provided for the cooler in compliance with chapter 6 of ICC A117.1.
f. A permanently mounted disposable cup dispenser shall be installed adjacent to the cooler with the dispensing end between 34" and 48" above finish floor and show the clear floor space complying to chapter 3 ICC A117.1 section 602.4.
4. PLUMBING DRAWINGS: The following plumbing fixtures are new. Please submit Plumbing sheet.
a. SERVICE SINK
i. The new service sink is showing on the Demolition Plan. Please remove it.
b. DRINKING FOUNTAIN
5. ENLARGED RESTROOM FLOOR PLAN
a. Clearance width around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall per ICC A117.1 sec 604.3.1
b. 604.3.2 Clearance depth around the water closet shall be 56 inches minimum in depth, measured perpendicular from the rear wall.
c. 604.3.3 The clearance overlap around the water closet shall be permitted to overlap the water closet, associated grab bars, paper dispensers, sanitary napkin receptacles, coat hooks, shelves, accessible routes, clear floor space at other fixtures and the turning space. No other fixtures or obstructions shall be within the required water closet clearance. FIGURE 604.3
6. CASHIER: provide drawings illustrating the following
a. Electrical/Communication: please include the cash counter power requirement on the electrical drawing.
b. The tops of dining surfaces & work surfaces shall be 28 inches min & 34 inches max above the floor per ICC A117.1 sec 902.4.
c. Sec 306.3.3 Knee clearance shall be 11 inches min in depth at 9 inches above the floor, and 8 inches min in depth at 27 inches above the floor.
d. Sec 306.2.4 Additional toe clearance space extending greater than 6 inches beyond the available knee clearance at 9 inches above the floor.
e. Sec 306.3 Knee clearance shall be 30 inches min in width.
f. 904.3.2 Parallel approach, the counter surface 36 inches min length.
g. 904.3.3 Forward approach, the counter surface 30 inches min length.
7. Please provide the Solar Heat Gain Coefficient and U value information for the glass storefront eh doors.
8. SECURED FILE
a. The file is secured. It is very hard to work with. Please submit a file that we can easily work with and unsecured.
9. Please resubmit.
03/12/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00260
ADDRESS/PARCEL: 3901 E GRANT RD Unit:UNIT 103 TUCSON, AZ 85712

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Does each suite have its own HVAC equipment? Please show all existing diffusers, thermostats, and mechanical equipment on the floor plan, including equipment sizes and CFM ratings. Reference: Section 107.2.1, IBC 2024.
2. Provide mechanical ventilation calculations demonstrating that the existing system is capable of supplying the minimum required outdoor air to each space. Reference: Section 403.3.1.1, IMC 2024.
03/12/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00260
ADDRESS/PARCEL: 3901 E GRANT RD Unit:UNIT 103 TUCSON, AZ 85712

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. The use of a point-of-use water dispenser in lieu of a drinking fountain requires the installation of a permanently mounted disposable cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor. See: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/2008-21_e_drinkingfountainpolicy.pdf
2. Will each unit have its own water heater? Please clarify the existing configuration and indicate the location of each water heater on the plans. Reference: Section 107.2.1, IBC 2024.
03/13/2026 Fire New Construction REVIEW COMPLETED
02/27/2026 PDSD Application Completeness Express REVIEW COMPLETED