Permit Number: TC-COM-0226-00258
Parcel: 133369690

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0226-00258
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2026 Commercial Electrical APPROVED
04/10/2026 Commercial Mechanical APPROVED
04/10/2026 Commercial Plumbing APPROVED
04/15/2026 Restamp Water - PDSD APPROVED
04/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/15/2026 Restamp Commercial Building PENDING ASSIGNMENT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
10. New Comment 4/15/2026. Please update the occupancy classification to remove the wording indicating (ASSEMBLY SOCIAL GATHERING) as this is a B Treat this as a typical note
11. New Comment 4/15/2026 Please update the Scope of work to include plumbing electric and mechanical if necessary. IBC 107.2.1
Previous Comment 8. Please amend the plans to provide the plumbing fixture calculations to determine the number of water closets and restrooms required for the occupant load. IBC 2902.1 The occupancy is a B and therefore the plumbing fixture count is based on B requirements, which would require a second bathroom. IBC 2901. As follows- 1 per 25 for the first 50 and 1 per 50 for the remainder exceeding 50
An appeal to the building official could be pursued requesting the use for use by all persons.
Previous Comment 9. IEBC 306.7 requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, a drinking fountain, and signs. Accessibility upgrades shall be required in accordance with IEBC.306.7. The water dispenser would count and the lav would count, but not the door relocation. Please show grab bars or reconfigure the bathroom space to allow for the 60 wide clear floor space for the water closet, 2017 ICC A117.1 604.3”

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/15/2026 Restamp Fire New Construction PENDING ASSIGNMENT
04/15/2026 Restamp Site Zoning PENDING ASSIGNMENT
04/15/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
10. New Comment 4/15/2026. Please update the occupancy classification to remove the wording indicating (ASSEMBLY SOCIAL GATHERING) as this is a B Treat this as a typical note
11. New Comment 4/15/2026 Please update the Scope of work to include plumbing electric and mechanical if necessary. IBC 107.2.1
Previous Comment 8. Please amend the plans to provide the plumbing fixture calculations to determine the number of water closets and restrooms required for the occupant load. IBC 2902.1 The occupancy is a B and therefore the plumbing fixture count is based on B requirements, which would require a second bathroom. IBC 2901. As follows- 1 per 25 for the first 50 and 1 per 50 for the remainder exceeding 50
An appeal to the building official could be pursued requesting the use for use by all persons.
Previous Comment 9. IEBC 306.7 requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, a drinking fountain, and signs. Accessibility upgrades shall be required in accordance with IEBC.306.7. The water dispenser would count and the lav would count, but not the door relocation. Please show grab bars or reconfigure the bathroom space to allow for the 60 wide clear floor space for the water closet, 2017 ICC A117.1 604.3”

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/01/2026 PDSD Application Completeness Express REVIEW COMPLETED