Permit Number: TC-COM-0226-00255
Parcel: 12003137A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0226-00255
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2026 Site Zoning Standard APPROVED
03/18/2026 Commercial Plumbing Standard NOT REQUIRED
03/11/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/27/2026 Site Engineering Standard NOT REQUIRED
03/18/2026 Water - PDSD Standard NOT REQUIRED
03/19/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/26/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding this review, please contact our team at PDSD-Permits@tucsonaz.gov

The address on the permit location does not match the unit number on the uploaded documents. Please submit a change of address request so that the unit numbers are reflected on the permit. For any unit not in our system, please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and add the units. If multiple units are having HVAC work done, each one will need a separate permit for the purpose of inspections.
03/19/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00255
ADDRESS/PARCEL: (851 W AJO WY Unit:BLDG 2 TUCSON, AZ 85713)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. EQUIPMENT LOCATION
a. Please locate/label the location of each external equipment for each apartment unit.
b. Provide a floor plan showing the location of the internal equipment for each apartment unit.
2. SEPARATE PERMIT FOR EACH APARTMENT UNIT
a. Each apartment unit shall have its own individual permit.
b. NOTE: Please coordinate with the city’s intake staff. It is possible to have one master drawing of which every unit can refer back to it. Separate permit for each unit removes confusion as to which unit has had its inspection conducted. Please contact Joseph Conrad at Joseph.Conrad@tucsonaz.gov
3. Please confirm the weight of the new HP HVAC as well as the weight of the Evap. Cooler being replace.
a. NOTE: Should the weight of the PH HVAC is more than the existing Evap. Cooler, structural calculation shall be required making sure the existing roof structure is able to handle the additional weight.
4. Please resubmit.
03/16/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0226-00255 (851 W AJO WY Unit:BLDG 2 TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

Plans shall include (as necessary for scope of work), but may not be limited to items below:
1. Provide an electrical plan showing the location of all electrical equipment, outlets, lighting fixtures, etc.
2. Provide electrical load calculations, for the Panel, Per NEC 220.40, demonstrating the existing electrical system can support the additional load.
3. Show all wiring methods in detail for all new electrical conductors and branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
4. Show a GFCI (NEC 210.8(B)(4)) receptacle outlet on the same level within 25’ of exterior HVAC equipment, NEC 210.63.
5. Provide a panel schedule, showing all circuits that are added. NEC arts;300 and 408.4. Include panel bus rating. IBC 107.1.
6. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixtures, receptacles, gate operator, equipment disconnect switch, etc., NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number.
7. HVAC disconnect per 424.19 Disconnecting Means..

Additional comments may be forthcoming with complete electrical plans for the proposed site and electrical work.
03/18/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00255
ADDRESS/PARCEL: 851 W AJO WY Unit:BLDG 2 TUCSON, AZ 85713

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Since the evaporative coolers are being replaced with heat pump units, please revise the plans to demonstrate compliance with the outdoor air ventilation and local exhaust requirements of Section 403.3.2 of the 2024 IMC. Clearly indicate how the proposed systems will meet the required ventilation and exhaust rates.

Also, a test and balance report is required to verify that the ventilation air flow rates comply with the code requirements.

2. Please provide heating/cooling load calculation for the building to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The efficiency rating of the replacement units will have to be equal to or exceed the minimum required by federal law for this geographic location.

3. Provide specifications for the proposed new A/C units and indicate their installation locations on the plans.
03/18/2026 Fire New Construction Standard REVIEW COMPLETED
02/26/2026 PDSD Application Completeness Express REVIEW COMPLETED