Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0226-00250
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2026 | Commercial Electrical Standard | APPROVED | |||
| 03/17/2026 | Site Zoning Standard | APPROVED | |||
| 03/17/2026 | Water - PDSD Standard | APPROVED | |||
| 03/12/2026 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 02/26/2026 | Site Engineering Standard | NOT REQUIRED | |||
| 03/18/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/17/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov 1. Provide plans with all sheets sealed by an Arizona Registrant . Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Please contact me if you have any questions about the above comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 03/17/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 2. Show that the walk-in cooler and the walk-in freezer meet the construction requirements of Section C403.10.2, IECC 2018. 3. Show that the walk-in cooler and the walk-in freezer meet the efficiency requirements of Section C403.10.2.1, IECC 2018. 4. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage (see details 7/M402 and 5/P403). Reference: Section 307.2.1, IMC 2024, as amended by the City of Tucson. 5. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2024 as amended by the City of Tucson. 6. The 55.0” wide rack oven hood (Type II) is specified to exhaust only 690 CFM. Provide the listing information for the hood that allows it to exhaust less than the required 200 CFM per linear foot of hood noted in Table 507.3.4.1, IMC 2024. Reference: Section 507.3.4, IMC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 03/17/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Kitchen floor drains shall discharge through a grease interceptor. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 03/18/2026 | Fire New Construction Standard | REQUIRES RESUBMIT | Resolve building review comments. Questions: patricia.shelton@tucsonaz.gov |
||
| 02/24/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |