Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0226-00247
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2026 Commercial Building Standard APPROVED
03/17/2026 Site Zoning Standard APPROVED
03/16/2026 Water - PDSD Standard APPROVED
03/06/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/26/2026 Site Engineering Standard NOT REQUIRED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
03/13/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0226-00247 (6330 E GOLF LINKS RD Unit:UNIT 170 TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Reference sheet E0.1, General Electrical Notes #43.
a. The provided equipment and room designations indicate that patient care will be provided in the ‘examination rooms’. These spaces are required to meet the requirement of NEC 517. See NEC 517.1, “This article applies to electrical construction and installation criteria in health care facilities that provide services to human beings.”
b. The wiring and electrical equipment in the examining rooms and other patient care areas within the office suite are subject to the requirements of Article 517.
2. Provide a clear list of services provided in these ‘examination rooms’ and the ‘triage’ room. Include any state licensing information associated with this installation.
03/16/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00247
ADDRESS/PARCEL: 6330 E GOLF LINKS RD Unit:UNIT 170 TUCSON, AZ 85730

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please ensure the code references are consistent. The energy code listed on the title sheet indicates the 2024 IECC, while Sheet M0.1 references the 2018 IECC. Revise the code reference on the title sheet.
2. Please update the Outdoor Air Calc Notes on Sheet M0.1 to reference the 2024 IMC.
03/16/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00247
ADDRESS/PARCEL: 6330 E GOLF LINKS RD Unit:UNIT 170 TUCSON, AZ 85730

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2024.
2. Please show that the distance from the hot water source (i.e., the recirculating loop) to the hot water termination for the public lavatory in the bathroom adjacent to the reception area complies with the requirements of Section C404.5, IECC 2018.
3. The water dispenser must be connected to a permanent supply of potable water and must be listed and labeled in accordance with the Code. It must be installed with a permanently mounted disposable cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor. See: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/2008-21_e_drinkingfountainpolicy.pdf
4. Please correct the section on the title sheet referencing the required plumbing fixtures. The occupant load is stated as 20; therefore, a service sink and drinking fountain are required. Reference: Section 2902.1, 2024 IBC.
02/24/2026 PDSD Application Completeness Express REVIEW COMPLETED