Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0226-00247
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/31/2026 | Commercial Electrical Standard | APPROVED | |||
| 04/14/2026 | Commercial Mechanical Standard | APPROVED | |||
| 04/14/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/14/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | The specified mounting shelf is capable of supporting the specified water heater. The question is, however, is the wall capable of supporting the shelf? Provide structural calculations to verify the wall can support the proposed load. [Initial comment: Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2024.] | ||
| 03/26/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |