Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0226-00240
Parcel: 12405023A

Address:
811 N EUCLID AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0226-00240
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2026 Historic APPROVED Proposed scope of work is for interior renovations only. Sheet A100 keynotes does state that all existing exterior doors, windows, and walls are to remain.
Historic review complete.
03/16/2026 Site Zoning Standard APPROVED
03/11/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/27/2026 Site Engineering Standard NOT REQUIRED
03/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/17/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov

1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
2. Please amend plans to show doors serving a space with ≥ 50 persons in A occupancies have panic hardware. IBC 1010.1.10
3. IEBC 306.7 requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, a drinking fountain, and signs. If these items are in full compliance with the current code, provide a statement indicating this on the cover sheet of the drawings. Otherwise, accessibility upgrades shall be required in accordance with IEBC.306.7. 1. If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs.

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
03/11/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0226-00240 (811 N EUCLID AV TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide a general electoral notes sheet which includes an electrical symbol and abbreviation legend.
3. Provide Ground Fault Protection for personnel per NEC 210.8(B)(2).
4. The #6 Cu conductor to the new Range appears to be undersized for the given 70A breaker, NEC 240.4.
5. Provide electrical load calculations, for the Panel ‘A’, Per NEC 220.40, demonstrating the existing electrical system can support the additional load.
6. Provide complete compliance with the 2018 IECC for the interior lighting, including sensors and lighting controls as required. (typically COMcheck).
03/16/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide general room exhaust for any cooking appliance in the warming kitchen that does not require the installation of a Type II hood (e.g., a convection oven). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 6, IMC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
03/16/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Clarify how the proposed 2” fixture drain for the 3-compartment sink is to be connected to the existing cleanout. Reference: Section 708.1.12, IPC 2018.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
03/18/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
03/16/2026 Water - PDSD Standard REQUIRES RESUBMIT Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
02/24/2026 PDSD Application Completeness Express REVIEW COMPLETED