Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0226-00236
Parcel: 12801001B

Address:
240 S WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0226-00236
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/18/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0226-00236 (240 S WILMOT RD TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide a minimum electrical lighting plan showing the location of the new lighting fixtures and conduit/conductor routing. Show connection point from exiting circuit to feed the new fixtures.
2. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor size/type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
02/18/2026 PDSD Application Completeness Express REVIEW COMPLETED