Permit Number: TC-COM-0226-00235
Parcel: 11706168A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0226-00235
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2026 Commercial Building Standard APPROVED
11/03/2026 Commercial Electrical Standard APPROVED
11/09/2026 Commercial Mechanical Standard APPROVED
11/09/2026 Water - PDSD Standard APPROVED
10/26/2026 Design Review Standard NOT REQUIRED Improvements are all indoors, so no RNA review is required.
11/03/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
10/21/2026 Site Engineering Standard NOT REQUIRED
11/06/2026 Site Zoning Standard NOT REQUIRED
11/12/2026 Commercial Post Review Express PENDING ASSIGNMENT
11/09/2026 Commercial Plumbing Standard REQUIRES RESUBMIT The drop-in hand sink, SS4.1, must be directly connected to the sanitary sewer. The attached ice bin must have a separate, indirect connection to the sanitary sewer with an air gap. Reference: Sections 301.3, 801.2, 802.1, and 802.3, IPC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
11/12/2026 Fire New Construction Standard REVIEW COMPLETED
10/21/2026 PDSD Application Completeness Express REVIEW COMPLETED